kVA vs kW: the difference and how to convert generator ratings

kW is the real power your equipment uses; kVA is the apparent power a generator must supply. kW = kVA × power factor, and generator ratings usually assume 0.8, so 100 kVA gives 80 kW.

Red, yellow, green, blue and black insulated cable cores crossing in loose curves on a dark background.

Close-up of insulated electrical cable cores (place and date not recorded). Image credit: "Close-up of Cables" by Antonio Avanti, Pexels License, via Pexels

To convert kVA to kW, multiply by the power factor: kW = kVA × power factor. Generator ratings usually assume a power factor of 0.8, so a 100 kVA set supplies 80 kW. To go from kW to kVA, divide by the power factor: 20 kW ÷ 0.8 = 25 kVA. Our advice: add up the kW of the equipment that runs at the same time, counting motors at their input power, divide by 0.8 (or by your loads' own power factor if it is lower) to get the minimum kVA, then check that the set can start your largest motor. Never compare a kW figure with a kVA figure directly.

How do you convert kVA to kW, and kW to kVA?

Multiply kVA by the power factor to get kW, and divide kW by the power factor to get kVA:

  • kW = kVA × power factor
  • kVA = kW ÷ power factor

Atlas Copco's generator sizing guide states that a standard power factor of 0.8 is assumed for most generators, "meaning that a generator rated at 100 kVA would deliver 80 kW of usable power". The LEOMAX LMF-16 on our 15 to 63 kVA silent diesel generator page shows the same ratio: it is listed as 15 kVA (12 kW) prime power, and 12 ÷ 15 = 0.8.

kVA to kW at a power factor of 0.8, and current per phase at 400 V three-phase (calculated)
Rating (kVA)Real power at 0.8 (kW)Current per phase at 400 V (A)
547.2
10814.4
151221.7
201628.9
302443.3
504072.2
6350.490.9
10080144.3
150120216.5
200160288.7
250200360.9
500400721.7

The table runs to 500 kVA because the MAINZ sets on our water-cooled diesel generator page cover about 15 to 500 kVA prime power. The table is calculated: the nameplate or datasheet of each generator gives its own figures and the power factor they assume, and if that power factor is not 0.8, use it instead. If you do not have the datasheet, ask us for technical details and datasheets, and we will send what applies to your request.

What should you check when comparing two generators?

Compare like with like:

  • The same unit. Convert with the power factor each datasheet states. Our site gives diesel generator ranges in kVA and petrol and inverter generator ranges in kW. If a datasheet or advert gives the same number in kVA and kW, either the set is rated at a power factor of 1.0 or the units are used loosely: ask for the prime rating in kW and the power factor it assumes.
  • The same rating. A set is sized on its prime power, the output it can deliver over long running hours; the standby figure applies for limited periods, such as a mains outage. A headline number may be the standby one: the LEOMAX LMW-33 we supply is 30 kVA prime and 33 kVA standby, and the 33 in its name matches the standby figure. If the set will run for many hours a day, compare prime ratings.
  • Rated output, not maximum. The MAINZ inverter generators on our inverter generators page are about 2.5 to 5 kW rated output and 2.8 to 5.5 kW maximum.
  • Voltage, phase and frequency. For example 400/230 V three-phase or 230 V single-phase, at 50 Hz or 60 Hz.
  • Site conditions. Atlas Copco notes that high temperatures can reduce a generator's output and call for derating, and a Cummins presentation on generator set selection that at higher altitudes or temperatures, less air may mean less engine power. For a hot plant room or a site in the mountains, tell us where the set will run, as our generators page asks.

What is the difference between kVA and kW?

kW (kilowatts) measures real power, the part that does useful work as heat, light or motion. kVA (kilovolt-amperes) measures apparent power: the voltage multiplied by the current, which is what a generator's alternator and the cables must carry. The ratio between the two is the power factor, a number between 0 and 1: power factor = kW ÷ kVA. Nameplates and datasheets often write it as PF or cos φ.

The gap between kVA and kW comes from reactive power, measured in kvar. Motors, transformers and some types of lighting need it to build their magnetic fields, but it does no useful work, so it raises the kVA without raising the kW, as the U.S. Department of Energy explains in its power factor fact sheet. Electric heaters and other resistive loads work at or close to a power factor of 1.0, so for them kVA and kW are almost equal.

kVA, kW and power factor at a glance
TermUnitWhat it tells you
Real (active) powerkWDoes the work; what your equipment consumes
Apparent powerkVAVoltage × current; what the alternator and cables carry
Reactive powerkvarBuilds the magnetic fields of motors and transformers; does no useful work
Power factorNo unit (0 to 1)kW ÷ kVA; 0.8 means 80% of the kVA is real power

Why are generators rated in kVA?

Because a generator set has two limits: its engine limits the kW it can supply, and its alternator limits the current, and therefore the kVA. Atlas Copco's guide says generators are rated in kVA because this unit "accounts for both active and reactive power components". The usual 0.8 comes from typical loads: Toromont Power Systems' note on generator power factor explains that average industrial loads include many motors, so 0.8 is the recognised standard.

The same note describes what happens on either side of 0.8. For a set rated 100 kVA at 0.8 (80 kW):

  • with loads at a power factor of 1.0, such as electric heaters, it supplies at most 80 kW, because the engine is the limit;
  • with loads at 0.7, it supplies at most 70 kW (100 × 0.7), because the alternator's current is the limit.

So if your loads include many motors that run well below their rated load, size on kVA using their real power factor, not 0.8.

Does three-phase change the conversion?

No. kW = kVA × power factor applies to single-phase and three-phase alike. Three-phase only changes how you work out kVA from the voltage and the current. The formulas Schneider Electric publishes are:

  • single-phase: kVA = volts × amps ÷ 1,000;
  • three-phase: kVA = 1.732 × volts × amps ÷ 1,000, where 1.732 is the square root of 3 and the voltage is measured between two phases (line to line).

To find the current, reverse the formula. In three-phase: amps = kVA × 1,000 ÷ (1.732 × volts).

Worked example: a 30 kVA set on a 400 V three-phase supply gives 30 × 1,000 ÷ (1.732 × 400) = about 43 A per phase and, at a power factor of 0.8, 24 kW. On a 400/230 V supply, each phase carries a third of the set's kVA: 230 V × 43 A ≈ 10 kVA. If your loads are single-phase, spread them across the three phases; loads on one phase alone can use only about a third of the set's rating.

What about motors, pumps and air conditioners?

They need more kVA than their nameplate kW suggests. A motor's rated power is the mechanical power at its shaft, as the U.S. Department of Energy's motor fact sheet explains. The electrical power it draws is higher, because of its efficiency, and the kVA is higher again, because of its power factor:

  • input kW = rated kW ÷ efficiency;
  • kVA = input kW ÷ power factor.

Example (illustrative values; read your motor's nameplate): a 5.5 kW pump motor with an efficiency of 88% and a power factor of 0.85 draws 5.5 ÷ 0.88 = 6.25 kW, and therefore needs 6.25 ÷ 0.85 = about 7.4 kVA. The same applies to lifts and air-conditioning compressors, which are also motor-driven.

Two more points matter for a generator. The Department of Energy notes that a motor's power factor falls when it runs well below its rated load. And starting takes far more. Atlas Copco says motors and transformers typically draw about six times their full-load current when they start, and that today's high-efficiency motors can draw almost double that. Cummins adds that a starting motor draws a high current at a low power factor. That is why our quote form asks for your largest motor and how it starts (direct on line, star-delta, soft starter or variable speed drive): send both.

How do you use kVA and kW to choose a generator size?

Work in kW first, then convert to kVA:

  • List the equipment you will power, with quantities and power in kW. For motors (pumps, lifts, air-conditioning compressors), use the input power, rated kW ÷ efficiency, as shown above, not the nameplate kW.
  • Add up only what runs at the same time.
  • Divide the total by 0.8, or by your loads' power factor if it is lower (for motors, the power factor on the nameplate or datasheet, where given), to get the minimum kVA.
  • Check that the set can start the largest motor, and allow for loads you plan to add.
  • Compare the result with the generator's prime rating.

Example: the equipment that runs together totals 20 kW, with motors counted at their input power. 20 ÷ 0.8 = 25 kVA, so a 20 kVA set is too small. Among the 15 to 63 kVA LEOMAX sets we supply, the next model up is the LMW-33, at 30 kVA prime (24 kW at 0.8, calculated). The start of the largest motor can still call for a larger set; the right size is confirmed in each quotation.

What should you send for a generator quotation?

Send the power you need, or the equipment you want to power. In our generator quote form, enter the power in kVA or kW and choose the unit, so the figure cannot be misread. If you are not sure, choose "Help me size it" and list your main equipment, as described in the sizing section of our generators page: we will recommend the size in our quotation. The form also asks for the voltage and phase, the frequency, the duty (standby for limited emergency hours, prime for unlimited hours at variable load, continuous for a constant load) and whether OTS should also arrange sea shipping.

OTS assembles and supplies generators and also trades generators from other brands. If the set will travel by sea, our guide FCL or LCL? lists what to tell us about a generator (fuel type, whether the tanks will be drained, batteries) and notes that it must be prepared and declared before loading.

Frequently asked questions

How many kW is 1 kVA?

At a power factor of 0.8, 1 kVA is 0.8 kW (800 W), and 1 kW needs 1.25 kVA. If the datasheet states another power factor, multiply the kVA by that factor instead.

Is a 10 kVA generator enough for 10 kW of equipment?

Usually not. If its rating assumes a power factor of 0.8, as most generator ratings do, a 10 kVA set supplies 8 kW, and 10 kW needs at least 12.5 kVA before you allow for motor starting. If its datasheet also says 10 kW, either the set is rated at a power factor of 1.0 or the units are used loosely: check the prime rating in kW before you buy.

Is kVA the same as kWh?

No. kVA and kW measure power at a given moment; kWh measures the energy used over time. A 2 kW load running for 3 hours uses 6 kWh.

How do I convert amps to kVA, and kVA to amps?

In single-phase, multiply volts by amps and divide by 1,000: 230 V × 10 A = 2.3 kVA. In three-phase, also multiply by 1.732, using the voltage between two phases. The other way round, each kVA gives about 1.44 A per phase at 400 V three-phase, and about 4.35 A at 230 V single-phase. So a 15 kVA three-phase set and a 5 kVA single-phase set both give about 21.7 A, but the three-phase set gives it on each of its three phases, so it supplies three times the power.

Sources

All pages read on 24 November 2026.

  1. OTS: Silent diesel generator sets, 15 to 63 kVA (our own page)
  2. OTS: Generators (our own page)
  3. OTS: Request a quote, generator form (our own page)
  4. OTS: Inverter generators (our own page)
  5. OTS: Water-cooled diesel generator sets (our own page)
  6. Atlas Copco: how to size a generator (generators guide)
  7. U.S. Department of Energy: Reducing power factor cost (fact sheet)
  8. U.S. Department of Energy: Determining electric motor load and efficiency (fact sheet)
  9. Schneider Electric: kVA and current for single- and three-phase transformers (FAQ, updated 17 September 2026)
  10. Cummins: Considerations for generator set selection (PowerHour presentation, 29 July 2021)
  11. Toromont Power Systems: Generator power factor (Consultant's Corner note; PDF created February 2004)

Related pages

Back to top

Not sure what size you need?

Choose the sizing option in the quote form and tell us about your loads. We will recommend the size in our quotation.

Quote list

Collect the products you are interested in, then send them to us in one request.

    Your quote list is empty.

    Add products or categories from their pages, then send everything in one request.

    Browse products

    Message us on WhatsApp